Initiate a shutdown sequence when an event occurs. A shutdown sequence is only initiated by events which are of
severe-level and warning-level type.
Initiated: Determines whether to request the computer to be shut down and the delay before initiating the
shutdown sequence. The shutdown will be canceled if the event is cleared during this delay time. The minimum
delay time to initiate shut down is based on the time set for the execution of the other actions to complete. This
includes the notify delay time, command delay time and command execution time.
As
This feature is used to apply identical settings to the particular event within the same category (Severe, Warning, and
Information). Once the As field of one event have been assigned, the settings of this event will use the assigned
event’s settings. The settings of this event will match with an assigned event’s.
The setting for the Local communication lost event would be copied from the settings of the UPS is faulty event
Event List
The Event List displays power events. The events displayed vary depending on whether they are listed in Agent or
Client and which UPS/PDU/ATS is providing the events.
Battery capacity is critically low - Battery capacity is critically low; power could be lost immediately.
Local communication lost in a power event. Communication with device has been lost during a power event.
Communication between the Agent and the UPS using the USB or serial cable has been lost during a power
failure.
Batteries are not present. Batteries are not present; the UPS cannot provide battery power in this condition.
Available runtime is insufficient. There is not sufficient runtime for a complete shutdown even if battery has fully
recharged.
This event will occur if the UPS has insufficient runtime (based off of the necessary shutdown time in the Event
Action page) for the Agent computer and all Client computers to shut down completely even if the batteries have
fully charged. An excessive load or long shutdown time may cause this event. Reduce some UPS load or set a
more accurate shutdown time to avoid this event occurrence.
Enters bypass mode. Entering bypass mode, battery power protection will no longer be provided.
Utility power failure. Utility power failure, battery power will be supplied.
Remaining runtime will be exhausted. Remaining runtime will be exhausted and is not sufficient for a complete
shutdown.
When the UPS switches to battery mode due to a power event, the battery power will be supplied to Agent
computer and all Client computers in order to shut down completely. If battery power consumption continues, the
remaining runtime will be exhausted. Agent and all Client computers should start a shutdown procedure
immediately.