Input is near overload. A PDU is near an overload condition.
The load level is near the maximum safe load for the PDU.
Input is overloaded. A PDU is in an overload condition.
The maximum safe load has been exceeded and the PDU is in an overload condition.
Shutdown time is insufficient. System shutdown time is insufficient.
After communication with the PDU is established and the outlet assignment is set up, the Client will detect whether
the connected outlet has sufficient time to allow for a shutdown. A sufficient shutdown time for the Client computer
requires at least the sum of the Necessary shutdown time option and shutdown delay time as configured in the
The output power is going to stop soon event.
More events are available for an ATS in Client:
Inputs both fail, ATS doesn’t switch input source. ATS doesn’t switch the source due to both input sources are
power failure.
When the current source of ATS is power failure, ATS attempts to switch to another source which is functioning
well. If both sources of ATS are power failure at the same time, the ATS cannot switch to another source.
Switch to redundant input source of ATS automatically. When the current source of ATS is power failure and
another redundant source is functioning well, ATS will switch to the redundant source to afford the power to its
load.
Redundant input source of ATS is power failure. The current source of ATS is functioning well, but the
redundant source is power failure. In this situation, once the current source is power failure, ATS cannot switch to
redundant source to afford power to its load.
ATS is faulty. ATS has malfunctioned in internal.
More events are available for the environment sensor within UPS/PDU/ATS in Client:
Environment sensor is no response. Environment sensor of the UPS/PDU/ATS has no response.. The sensor
may be malfunction or removal from the UPS/PDU/ATS.
Environment temperature is overheated. The temperature is measured by the sensor exceeds the high
threshold.
Environment temperature is undercooled. The temperature is measured by the sensor violates the low
threshold.
Environment humidity is over wet. The relative humidity is measured by the sensor exceeds the high threshold.
Environment humidity is overdried. The relative humidity is measured by the sensor violates the low threshold.
Principles for Client Firing Events
If both power sources of the ATS which connects with Client can be provided power by two UPS, the UPS event will
be fired in the events of two power sources failure at the same time. If there is one single or none UPS providing
power to the ATS, the event will be fired in case of power failure.
Note: In Client, events will be divided into categories according to its power connection. Each event has the individual
settings for each category.