community with write permission, and public with read only permission. The community used by the Client to access
the UPS RMCARD/PDU/ATS must have a minimum of read permission for basic operation. If the community has write
permission, the Client can complete some configuration tasks automatically.
If the Client cannot complete these tasks due to a permission limitation, the following settings must be configured
manually in the UPS RMCARD web or in the PDU web:
Note: The community can be configured on the Network/Access Control (or Network Service/SNMPv1 Service)
page in the UPS remote management card (RMCARD) web or on the Network/SNMP Settings (or Network
Service/SNMPv1 Service) page in the PDU web.
Outlet Off Delay Setting - Specify the necessary time for the Client to shut down the computer on the
Outlet/Outlet Configuration page in the PDU web.
Add the IP address of the Client computer to the Trap Receiver list of the UPS RMCARD/PDU/ATS on the
Network/Trap Notification page in the UPS RMCARD web or in the PDU web.
Network/Access Control page in the UPS RMCARD201 web
SNMP Trap Community: The Client uses the community to authenticate the SNMP trap from a secure device. The
community default is public. The IP address of the Client computer must be added to the Trap Receiver list on the
Network/Trap Notification page of the UPS RMCARD and the PDU to ensure the community is matched.